Download Installation Checklist
Download Quick Start Guide
Download Operating Manual
Download Cut Sheet
Download HGM Multi-Zone & Single-Zone Gas List
Download Multi-Zone Refrigerant Gas Library
Main PCB Replacement Instructions
Multi-Zone Gas Monitor
Industry Leading Precision Monitoring for Low-level Gas Leak Detection.
MSA Bacharach’s Multi-Zone Gas Monitor provides precise measurements enabling early leak detection for compliance with refrigeration safety codes (ASHRAE 15, EN 378, CSA-B52) and emissions reduction standards (F-Gas, CARB).
- Proprietary infrared (NDIR) sensor accurately detects the presence of a target gas down to an industry-leading 1 ppm Minimum Detection Level (MDL)
- Sensor is not prone to false alarms caused by cross-interference from other gases or sudden changes in temperature or humidity
- Gas library contains 60+ refrigerants, including CFCs, HFCs, HCFCs, HFOs and natural refrigerants (R-744, R-717)
- Backlit display shows real-time concentration readings and makes configuration and self-diagnostics intuitive
- Capable of monitoring up-to 16 zones (expandable up to 48 sample points) and detecting multiple gases with a single monitor
- Two optional analog outputs (4-20mA) and Modbus communications (slave) for integration with third-party BMS / BAS control systems
- Three user-configurable relays (leak, spill and evacuate) may be used to activate external beacons / sounders, ventilation or other countermeasures
MSA Bacharach’s Multi-Zone Gas Monitor delivers the best refrigerant leak detection available, with industry-leading MDL of 1ppm for halogenated gases, the fastest sampling frequency and the widest range of refrigerants accurately detected. The large graphic LCD display and LED status indicators provide a system-wide overview at a glance.
The Multi-Zone enhances effective refrigerant management and ensures compliance with refrigeration safety standards (ASHRAE 15, EN 378, CSA-B52) and emissions regulations (F-Gas, CARB RMP). It detects leaks early to enable cost savings by reducing refrigerant recharge, enhancing energy efficiency and reducing risk of refrigeration failure and produce loss. A variety of communication interfaces are available including Modbus, BACnet and LonWorks, allowing easy integration into BMS / BAS systems and remote monitoring solutions.
Product Specifications
- Sensor Channels: 4 to 16
- Sample Points: 48
- Measuring Range: Refrigerants: 0 to 10,000 ppm, Ammonia: 25 to 10,000 ppm Carbon Dioxide: 300 to 8,000 ppm
- Sensitivity / Minimum Detection Limit: Refrigerants: 1 ppm, Ammonia: 10 ppm, Carbon Dioxide: 10 ppm
- Accuracy: ±1 ppm ±10% from 0-1000 ppm (refrigerants); ±10 ppm ±10% from 0-10,000 ppm (Ammonia); ±5 PPM ±5% from 300-1000 ppm (CO2)
- Resolution: 1 ppm
- Enclosure Rating: General Purpose
- Sampling Distance: 0 to 1,200' (0 to 365 m)
- User Interface: Backlit, graphic LCD 160 x 128 pixel; three status LEDs
- Power: 100 to 240 VAC, 50/60 Hz, 20W
- Analog Communications: 4 to 20 mA (optional)
- Digital Communications: Modbus RTU via RS-485
- Operating Voltage: 100 to 240 VAC, 50 / 60 Hz
- Relay Rating: 3 alarm relays, 1 fault relay, SPDT
- Wiring: 5 A @ 250 VAC, resistive load
- Alarm: Integrated Audible / Visual Alarm
- Ambient Temperature: 32 to 122°F (0 to 50°C)
- Humidity: 5 to 90 %RH, non condensing
- Altitude: 0 to 6,560 ft (2,000 m)
- Status Indicator: LCD, LEDs
- Buzzer Volume: 80 dB @ 10 cm
- Product Dimensions (L×W×H): 13.7” × 12.3” × 5” (350 × 315 × 130 mm)
- Product Weight: 15 lbs. (6.8 kg)
- Sensor Type: NDIR
- Expected Sensor Service Life: 10 Years
- Approvals: CE, UL, CSA, EN 61010-1, EN 61326, EN 14624
- Warranty: 2 Years
- Country of Origin: United States
- Part Number: 3015-5046
Same Leak Detector as Copeland Emerson part 808-2016
When the refrigerant library needs be updated, you can download the Firmware Upgrade Utility found in the Technical Library section on the Multi-Zone Gas Monitor product page here.
Compatible with MSA Bacharach Pressure Regulator 3015-3849.